FACP Activations Appendix A: MS-5210UD
ACM-8RF PN 50362:C 03/21/01
23
Alarm and Trouble Activation
Table 5 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for alarm and trouble activation. Note that a
maximum of five ACM-8RFs are required if relays are to be designated to
trigger on any FACP status change. If system status relays are not required,
three ACM-8RFs may be used to allow individual relay triggering for alarm
and trouble activation of FACP zones 1 through 10. When using only three
ACM-8RFs, be sure to use the switch settings for the 3rd, 4th and 5th
ACM-8RF in Table 5.
Table 5 SW3 Settings for Alarm and Trouble
MS-5210UD
Zone
ACM-8RF
Alarm Relay
ACM-8RF Trouble
Relay
SW3 Settings
System Status 1=System Alarm 5=System Trouble
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF
System Status Relay 2 (not used) Relay 6 (not used)
System Status Relay 3 (not used) 7=System Off Normal
System Status Relay 4 (not used) 8=System Supervisory
System Status Relay 1 (not used) 5=NAC(s) Fault
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF
System Status Relay 2 (not used) 6=Walktest Start
System Status Relay 3 (not used) 7=Battery Fail
System Status Relay 4 (not used) 8=AC Fail
Z1 Relay 1 Relay 5
3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others = OFF
Z2 Relay 2 Relay 6
Z3 Relay 3 Relay 7
Z4 Relay 4 Relay 8
Z5 Relay 1 Relay 5
4th ACM-8RF
SW3-4 = ON
SW3-5 = ON
All others = OFF
Z6 Relay 2 Relay 6
Z7 Relay 3 Relay 7
Z8 Relay 4 Relay 8
Z9 Relay 1 Relay 5
5th ACM-8RF
SW3-1 = ON
SW3-6 = ON
All others = OFF
Z10 Relay 2 Relay 6
n/a Relay 3 (not used) Relay 7 (not used)
n/a Relay 4 (not used) Relay 8 (not used)