Alarm and Trouble Activation
When “Alarm/Trouble” is selected, relays 1 - 4 respond to alarm signals and
relays 5 - 8 respond to trouble signals.
The following table displays an example of how to set the DIP switches on four
(4) ACM-8RFs to annunciate the zones of an annunciator address. Although
this table shows System Points & Zones 1 to 8 (address 01), by referring to Table
13 on page 38 it can be determined which ACM-8RF will activate what zone
or point, depending on the address that is set on the rotary switches.
Table 17 SW3 Settings for Alarm/Trouble - Zones
Note: If the System Points (system alarm, trouble or silence etc.) is not required, up to
fourteen (14) ACM-8RFs may be used to allow activation of FACP zones 1 through 56.
When using this configuration do not use the DIP Switch settings for the 1st ACM-8RF.
ACM-8RF
Alarm Relay
MS-9600 Zone
ACM-8RF
Trouble Relay
MS-9600 Zone
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF
1=System Alarm System Point 5=System Trouble System Point
2 (not used) System Point Relay 6 (not used) System Point
3 (not used) System Point 7=System Off Normal System Point
4 (not used) System Point 8=System Supervisory System Point
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF
1 (not used) System Point 5=NAC Fault System Point
2 (not used) System Point 6=Walktest Start System Point
3 (not used) System Point 7=Battery Fail System Point
4 (not used) System Point 8=AC Fail System Point
3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others = OFF
Relay 1 Zone 1 Relay 5 Zone 1
Relay 2 Zone 2 Relay 6 Zone 2
Relay 3 Zone 3 Relay 7 Zone 3
Relay 4 Zone 4 Relay 8 Zone 4
4th ACM-8RF
SW3-4 = ON
SW3-5 = ON
All others = OFF
Relay 1 Zone 5 Relay 5 Zone 5
Relay 2 Zone 6 Relay 6 Zone 6
Relay 3 Zone 7 Relay 7 Zone 7
Relay 4 Zone 8 Relay 8 Zone 8