Appendix B: MS-9200 FACP Activations
32
ACM-8RF PN 50362:C 03/21/01
FACP Activations
DIP switch SW3 on the ACM-8RF Relay Control Module is used to determine
which FACP activations will trigger relays on the ACM-8RF. Use the following
tables to set SW3 switches. The Address Select Rotary Switches on all ACM-
8RFs must be set to address ‘01’ (SW1 = 0, SW2 = 1).
Two tables are provided, one table for alarm only operation (SW4-1 = ON) and
one table for alarm and trouble operation (SW4-1 = OFF).
Alarm Only Activation
Table 10 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for MS-9200 alarm activation only. A
maximum of eight ACM-8RFs are required if one relay is to be designated to
trigger on any FACP zone alarm. If a general system alarm relay is not required,
seven ACM-8RFs may be used to allow individual relay triggering for alarm
activation of FACP zones 1 through 56. When using seven ACM-8RFs, be sure
to use the switch settings for the 2nd through the eighth ACM-8RF in Table 10.
Table 10 SW3 Settings for Alarm Only
MS-9200 Zone
ACM-8RF
Relay
ACM-8RF
SW3 Settings
MS-9200
Zone
ACM-8RF
Relay
SW3 Settings
System Alarm Relay 1
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others =
OFF
Z25 Relay 1
5th ACM-8RF
SW3-1 = ON
SW3-6 = ON
All others =
OFF
Not Used Relay 2 Z26 Relay 2
Not Used Relay 3 Z27 Relay 3
Not Used Relay 4 Z28 Relay 4
Not Used Relay 5 Z29 Relay 5
Not Used Relay 6 Z30 Relay 6
Not Used Relay 7 Z31 Relay 7
Not Used Relay 8 Z32 Relay 8
Z1 Relay 1
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others =
OFF
Z33 Relay 1
6th ACM-8RF
SW3-2 = ON
SW3-6 = ON
All others =
OFF
Z2 Relay 2 Z34 Relay 2
Z3 Relay 3 Z35 Relay 3
Z4 Relay 4 Z36 Relay 4
Z5 Relay 5 Z37 Relay 5
Z6 Relay 6 Z38 Relay 6
Z7 Relay 7 Z39 Relay 7
Z8 Relay 8 Z40 Relay 8
Z9 Relay 1
3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others =
OFF
Z41 Relay 1
7th ACM-8RF
SW3-3 = ON
SW3-6 = ON
All others =
OFF
Z10 Relay 2 Z42 Relay 2
Z11 Relay 3 Z43 Relay 3
Z12 Relay 4 Z44 Relay 4
Z13 Relay 5 Z45 Relay 5
Z14 Relay 6 Z46 Relay 6
Z15 Relay 7 Z47 Relay 7
Z16 Relay 8 Z48 Relay 8
Z17 Relay 1
4th ACM-8RF
SW3-4 = ON
SW3-5 = ON
All others =
OFF
Z49 Relay 1
8th ACM-8RF
SW3-4 = ON
SW3-6 = ON
All others =
OFF
Z18 Relay 2 Z50 Relay 2
Z19 Relay 3 Z51 Relay 3
Z20 Relay 4 Z52 Relay 4
Z21 Relay 5 Z53 Relay 5
Z22 Relay 6 Z54 Relay 6
Z23 Relay 7 Z55 Relay 7
Z24 Relay 8 Z56 Relay 8